ESO 3.6m Telescope

Servo Adjustment

 
<>
About the 3.60m TelescopeAbout the CAT Telescope
General
News
       

PRESET ADJUSTMENTS

  • Note
    • All adjustments must be made in the order indicated.
    • If power amplifiers are being adjusted, carry out all power amplifier settings first.
    • Servo System Offset (5) may be adjusted as required, always adjust after setting power amps.
    • DO NOT ADJUST P2 AND P4 ON THE PID UNIT AT ANY TIME.
    • All measurements except step (8) are made at a telescope elevation of > 15
    • All measurements are made with respect to ground.
  Parameter Adjust for Preset Location Measuring Point Switch Condition
1 Tacho Summing Offset Tacho FB = 0 volts Monitor P1 Servo Interface AK Supply to the
2 Current Monitor Offset 0/P = 0 volts P4 Servo Interface BT Power Amplifiers
3 Acceleration Offset Acceleration FB=0 volts P3 Servo Interface BD Switched OFF
4 Ramp Circuit Offset Ur = 0 volts P2 Ramp Circuit AL S=0
5 Servo System Offset Power Amp. 0/P = 0 volts P3 PID Unit Power Amp Output S=0
6 Preload current Motor current = 10 A * P2 Servo Interface Motor Ammeters S=0
7 Maximum Slew rate Tacho FB=+/- 2.5 volts P1 PID unit BA +/- S (3 sec. delay)
8 Slew rate at < 15° Ui +/- 2.5 volts P3 Ramp Circuit Ui (on PCB) +/- S ar <15°
9 Acceleration ramp Ur= see fig. 1 P1 Ramp Circuit AL S=0 initially then +S, or -S

Fig. 1

 

     

 

    