Alpha - Delta Lock Pins
Symptom: Lock pin does not move manually
|
Yes |
No |
|
|
In Aux. Functions Panel, is switch in Off-line position? |
Check the Motor Enabled LED |
Change to Off-line |
|
Is the Motor Enable LED ON |
Check the MCB Local/Remote switch |
Check for a Motor Protection condition |
| Is the MCBx in the Local mode? | Go to MCBx and try to move motor from there. Remember to switch to OFF-LINE mode in MCB | Change switch to Local Mode |
| Is the Motor Protection LED ON? | Go to MCBx and clear the Motor Protection condition | |
|
Is there an interlock condition in the MBC (led off)? |
Try to clear the interlock condition. If it is a false interlock, put a jumper in the by-pass terminal |
Check that the telescope at the locking position (12 hrs., -29°, Platform) |
Lock Pin Alpha MCBF
Lock Pin Delta Zenith MCBM
Lock Pin Delta Platform MCBM