Signal name |
Function: |
Relay |
TS16 |
Cable |
To |
|
Connector |
Pin |
|||||
|
Inputs to interlock system |
|
|
|
|
|
ILLSALEAST-R |
Not at east limit, from telescope (F1) |
RL8 |
1 |
R11-8 |
H16 (R1J1) |
6 |
|
24V return |
|
130 |
R11-8 |
H16 (R1J1) |
5 |
ILAL12HR-R |
Alpha at 12h, from telescope (k) |
RL18 |
2 |
R11-8 |
H16 (R1J1) |
12 |
|
24V return |
|
131 |
R11-8 |
H16 (R1J1) |
13 |
ILLSALWEST-R |
Not at west limit, from telescope (F2) |
RL9 |
3 |
R11-8 |
H16 (R1J1) |
14 |
|
24V return |
|
132 |
R11-8 |
H16 (R1J1) |
15 |
ILPAAL1120-R |
Alpha PA1 temperature OK |
RL4 |
4 |
218 |
C (PA1alp) |
2 |
|
24V return |
|
133 |
218 |
C (PA1
alp) |
1 |
ILPAAL120A-R |
Alpha PA1 overcurrent protection OK |
RL6 |
5 |
218 |
C (PA1
alp) |
6,7 |
|
24V return |
|
134 |
218 |
C (PA1 alp) |
3 |
|
GND |
|
193 |
218 |
C (PA1
alp) |
9 |
|
Bridge |
|
8 |
218 |
C (PA1 alp) |
4,5 |
ILPAAL2120-R |
Alpha PA2 temperature OK |
RL5 |
6 |
219 |
C (PA2
alp) |
2 |
|
24V return Dsds |
|
135 |
219 |
C (PA2
alp) |
1 |
ILPAAL220A-R |
Alpha PA2 overcurrent protection OK |
RL7 |
7 |
219 |
C (PA2
alp) |
6,7 |
|
24V return |
|
136 |
219 |
C (PA2 alp) |
3 |
|
GND |
|
194 |
219 |
C (PA2
alp) |
9 |
|
Bridge |
|
9 |
219 |
C (PA2 alp) |
4,5 |
ILALOILP-R |
Alpha oil pressure OK (o4) |
RL1 |
10 |
205 |
D (tel hydr) |
2 |
|
GND return |
|
191 |
205 |
D (tel hydr) |
1 |
ILALLUBE-R |
Alpha lubrication pressure OK, REVERSE LOGIC! (o2) |
RL2 |
11 |
217 |
G (alp P dist) |
2 |
|
24V return |
|
138 |
217 |
G (alp P dist) |
1 |
ILLSDENORT-R |
Not at north limit, from telescope (F1) |
RL31 |
12 |
R21-18 |
H15 (PBXF1) |
4 |
|
24V return |
|
125 |
R21-18 |
H15 (PBXF1) |
3 |
ILLSDE<-90-R |
Delta < -90 degrees, from telescope (J4) |
RL36 |
13 |
R21-18 |
H15 (PBXF1) |
6 |
|
24V return |
|
126 |
R21-18 |
H15 (PBXF1) |
7 |
ILLSDE-120-R |
Delta > -120 degrees, from telescope (J3) Sdasdssdsddad |
RL20 |
14 |
R21-18 |
H15 (PBXF1) |
8 |
|
24V return |
|
127 |
R21-18 |
H15 (PBXF1) |
11 |
ILLSDESOUT-R |
Not at south limit, from telescope (F2) |
RL32 |
18 |
R21-18 |
H15 (PBXF1) |
14 |
|
24V return |
|
129 |
R21-18 |
H15 (PBXF1) |
15 |
ILPADE1120-R |
Delta PA1 temperature OK |
RL27 |
19 |
202 |
C (PA1
del) |
2 |
|
24V return |
|
139 |
202 |
C (PA1
del) |
1 |
ILPADE120A-R |
Delta PA1 overcurrent protection OK |
RL29 |
20 |
202 |
C (PA1
del) |
6,7 |
|
24V return |
|
140 |
202 |
C (PA1
del) |
3 |
|
GND |
|
195 |
202 |
C (PA1
del) |
9 |
|
Bridge |
|
23 |
202 |
C (PA1
del) |
4,5 |
ILPADE2120-R |
Delta PA2 temperature OK |
RL28 |
21 |
203 |
C (PA2
del) |
2 |
|
24V return |
|
141 |
203 |
C (PA2
del) |
1 |
ILPADE220-R |
Delta PA2 overcurrent protection OK |
RL30 |
22 |
203 |
C (PA2
del) |
6,7 |
|
24V return |
|
142 |
203 |
C (PA2
del) |
3 |
|
GND |
|
196 |
203 |
C (PA2
del) |
9 |
|
Bridge |
|
24 |
203 |
C (PA2
del) |
4,5 |
ILDEOILP-R |
Delta oil pressure OK (o3) |
RL24 |
25 |
216 |
E (tel
hydr) |
2 |
|
GND return |
|
192 |
216 |
E (tel hydr) |
1 |
ILDELUBE-R |
Delta lubrication pressure OK (o1) |
RL25 |
26 |
204 |
G (del
P dist) |
2 |
|
24V return |
|
146 |
204 |
G (del P dist) |
1 |
ILEMPRIM-R |
Prime focus area emergency OK (r1) |
RL13 |
27 |
F002 |
B28 (DBXF) |
11 |
ILEMCENT-R |
Center section emergency OK (r2) |
RL14 |
28 |
F002 |
B28 (DBXF) |
12 |
ILEMCAGE-R |
Cassegrain cage area emergency OK (r3) |
RL15 |
29 |
F002 |
B28 (DBXF) |
13 |
ILEMPLAT-R |
Platform area emergency OK (r4) |
RL16 |
30 |
F002 |
B28 (DBXF) |
14 |
ILBALL15-R |
Tube above 15 degrees, from ball switch (h1) |
RL33 |
31 |
F002 |
B28 (DBXF) |
15 |
ILBALL07-R |
Tube above 7 degrees, from ball switch (h2) |
RL38 |
32 |
F002 |
B28 (DBXF) |
16 |
ILBALL06-R |
Tube above 6 degrees, from ball switch (h3) |
RL21 |
33 |
F002 |
B28 (DBXF) |
17 |
ILCARBAK-R |
Platform carriage is back (Z1) |
RL12 |
34 |
F002 |
B28 (DBXF) |
18 |
ILALLOCI-R |
Alpha lock pin is in (n1) |
RL22 |
35 |
F002 |
B28 (DBXF) |
19 |
ILALLOCO-R |
Alpha lock pin is out (n2) |
RL3 |
36 |
F002 |
B28 (DBXF) |
20 |
ILDELOCO-R |
Delta lock pin is out (m2) |
RL26 |
37 |
F002 |
B28 (DBXF) |
21 |
ILRADPAD-R |
Radial pads (Sa1) |
n.c. |
38 |
F002 |
B28 (DBXF) |
22 |
ILAIRCLA-R |
Air pressure clamps (Sa2) |
RL10 |
39 |
F002 |
B28 (DBXF) |
23 |
|
GND |
|
152 |
F002 |
B28 (DBXF) |
26 |
|
|
|
|
|
|
|
|
Local inputs |
|
|
|
|
|
ILLRESET-R |
Interlock latch reset button |
RL1 |
40 |
- |
Front panel |
- |
ILEMLOCL-R |
Emergency button on interlock rack |
RL17 |
41 |
- |
Front panel |
- |
WATCHDOG-R |
VME Watchdog |
RL11 |
42 |
tbd bd |
VME rack |
tbd |
ALPD24V |
24V power supply |
|
97 |
210 |
H (alp P dist) |
1,2 |
|
GND |
|
156 |
210 |
H (alp P dist) |
3,4 |
DEPD24V |
24V power supply |
|
98 |
211 |
H (del
P dist) |
1,2 |
|
GND |
|
155 |
211 |
H (del P dist) |
3,4 |
|
Main outputs |
|
|
|
|
|
ALOILLUB-C |
Alpha lubrication command |
RL19 |
99 |
217 |
G (alp P dist) |
3 |
|
GND |
|
189 |
217 |
G (alp P dist) |
4 |
DEOILLUB-C |
Delta lubrication command |
RL19 |
100 |
204 |
G (del
P dist) |
3 |
|
GND |
|
190 |
204 |
G (del P dist) |
4 |
ILLSAL12HR-C |
Alpha at 12h |
RL18 |
45 |
F002 |
B28 (DBXF) |
3 |
|
24V to alpha control |
|
143 |
248 |
C (alp contrl) |
1 |
|
GND |
|
153 |
248 |
C (alp contrl) |
2 |
ILBALL15+-C |
Telescope above 15 degrees |
RL33 |
47 |
248 |
C (alp contrl) |
3 |
|
Floating return for following 2 signals |
|
48 |
248 |
C (alp contrl) |
4 |
ILALEAST-C |
East limit |
RL8 |
49 |
248 |
C (alp contrl) |
6 |
ILALWEST-C |
West limit |
RL9 |
50 |
248 |
C (alp contrl) |
7 |
ILPAALENAB-C |
Alpha interlock complete |
RL23 |
56 |
248 |
C (alp
contrl) |
9 |
|
24V to delta control |
|
144 |
254 |
C (del
contrl) |
1 |
|
GND |
|
154 |
254 |
C (del
contrl) |
2 |
ILBALL15+-C |
Telescope above 15 degrees |
RL33 |
51 |
254 |
C (del
contrl) |
3 |
ILDEDIRCOM-C |
Delta direction enable common |
RL36 |
52 |
254 |
C (del
contrl) |
4 |
ILDEDIRNOR-C |
Delta north direction enable |
RL36 |
53 |
254 |
C (del
contrl) |
6 |
ILDEDIRSOU-C |
Delta south direction enable |
RL36 |
54 |
254 |
C (del
contrl) |
7 |
ILOVER24V |
24V for override key to control |
n.c. |
55 |
254 |
C (del
contrl) |
5 |
ILPADEENAB-C |
Delta interlock complete to control |
RL37 |
57 |
254 |
C (del
contrl) |
9 |
ILPAALENAB-C |
Alpha interlock complete to power distribution |
RL23 |
56 |
210 |
H (alp P dist) |
5 |
ILPADEENAB-C |
Delta interlock complete to power distribution |
RL37 |
57 |
211 |
H (del
P dist) |
5 |
|
|
|
|
|
|
|
|
Status outputs to VME |
|
|
|
|
|
ILALLUBE-C |
Alpha lubrication OK |
RL2 |
58 |
ISTAT |
TS22 |
1 |
ILALOILP-C |
Alpha oil pressure OK |
RL1 |
59 |
ISTAT |
TS22 |
2 |
ILPAAL1120-C |
Alpha PA1 temperature OK |
RL4 |
60 |
ISTAT |
TS22 |
3 |
ILPAAL120A-C |
Alpha PA1 current OK |
RL6 |
61 |
ISTAT |
TS22 |
4 |
ILPAAL2120-C |
Alpha PA2 temperature Ok |
RL5 |
62 |
ISTAT |
TS22 |
5 |
ILPAAL220A-C |
Alpha PA2 current OK |
RL7 |
63 |
ISTAT |
TS22 |
6 |
ILLSALWEST-C |
Not at west limit |
RL9 |
64 |
ISTAT |
TS22 |
7 |
ILLSALEAST-C |
Not at east limit |
RL8 RL6 |
65 |
ISTAT |
TS22 |
8 |
ILALLOCO-C |
Alpha lock pin is out |
RL3 |
66 |
ISTAT |
TS22 |
9 |
ILDELUBE-C |
Delta lubrication OK |
RL25 |
67 |
ISTAT |
TS22 |
10 |
ILDEOILP-C |
Delta oil pressure OK |
RL24 |
68 |
ISTAT |
TS22 |
11 |
ILPADE1120-C |
Delta PA1 temperature Ok |
RL27 |
69 |
ISTAT |
TS22 |
12 |
ILPADE120A-C |
Delta PA1 current OK |
RL29 |
70 |
ISTAT |
TS22 |
13 |
ILPADE2120-C |
Delta PA2 temperature OK |
RL28 |
71 |
ISTAT |
TS22 |
14 |
ILPADE220A-C |
Delta PA2 current OK |
RL30 |
72 |
ISTAT |
TS22 |
15 |
ILLSDESOUT-C |
Not at south limit |
RL32 |
73 |
ISTAT |
TS22 |
16 |
ILLSDENORT-C |
Not at north limit |
RL31 |
74 |
ISTAT |
TS22 |
17 |
ILDELOCO-C |
Delta lock pin out |
RL26 |
75 |
ISTAT |
TS22 |
18 |
ILAIRCLA-C |
Air clamps active |
RL10 |
77 |
ISTAT |
TS22 |
19 |
ILEMPRIM-C |
Primary area OK |
RL13 |
78 |
ISTAT |
TS22 |
20 |
ILEMCENT-C |
Center section OK |
RL14 |
79 |
ISTAT |
TS22 |
21 |
ILEMCAGE-C |
Cassegrain cage area OK |
RL15 |
80 |
ISTAT |
TS22 |
22 |
ILEMPLAT-C |
Platform area OK |
RL16 |
81 |
ISTAT |
TS22 |
23 |
ILBALL15-C |
Tube above 15 degrees |
RL33 |
82 |
ISTAT |
TS22 |
24 |
ILBALL07-C |
Tube above 7 degrees |
RL38 |
83 |
ISTAT |
TS22 |
25 |
ILBALL06-C |
Tube above 6 degrees |
RL21 |
84 |
ISTAT |
TS22 |
26 |
ILCARBAK-C |
Platform carriage back |
RL12 |
86 |
ISTAT |
TS22 |
27 |
ILAL12HR-C |
Alpha at 12h position |
RL18 |
87 |
ISTAT |
TS22 |
28 |
ILLSDE-120-C |
Delta > -120 degrees |
RL20 |
90 |
ISTAT |
TS22 |
29 |
ILLSDE<-90-C |
Delta < -90 degrees |
RL36 |
91 |
ISTAT |
TS22 |
30 |
ILOVERRD-C |
Interlock not overridden |
S2 |
92 |
ISTAT |
TS22 |
31 |
ILALLOCI-C |
Alpha lock pin is in |
RL22 |
93 |
ISTAT |
TS22 |
32 |
ILEMLOCL-C |
Emergency switch on interlock rack OK |
RL17 |
94 |
ISTAT |
TS22 |
33 |
ILPAALENA-C |
Alpha interlock complete |
RL23 |
95 |
ISTAT |
TS22 |
34 |
ILPADEENA-C |
Delta interlock complete |
RL37 |
96 |
ISTAT |
TS22 |
35 |
|
GND |
|
157 |
ISTAT |
TS22 |
36 |
![]() ![]() ![]() ![]() ![]() ![]() ![]() |