The Hydrostatic Bearing VME system provides interfacing to the following
subsystems:
The following sections refer to specific information:
The Hydrostatic Bearing control comprises a local PLC controller, provided by the company INNSE. A VME system, provided by ESO, controls this PLC. This chapter describes only the interface signals between the ESO computer and the PLC. For detailed information on the PLC, refer to the INNSE documentation listed in Subsection 7.4.3.
Interlock for Azimuth Motion
The azimuth motion is interlocked if the oil pressure behind the valve is too low.
Emergency stop buttons in the building are routed to the Hydrostatic Bearing VME rack. Here, each button generates a computer signal.
The signals to and from the Hydrostatic Bearing controller are connected to the VME computer via opto-couplers. This is done to interface from 24V logic to 5V logic and to provide galvanic separation.
The signals from the Hydrostatic Bearing side are 24V true in most cases. The opto-couplers invert the signals; therefore the VME I/O signals are 0V true in most cases. The signals are described in the true state (as normal). The false state is indicated, in the cases where it is not ovbious, with an "f".
In all cases, the description in the documents is defined such that:
The signals in the Hydrostatic Bearing subsystem are divided into the
following groups that indicate where the signals originate (inputs to the
computer), or where they have to be routed (outputs from the computer).
Refer to the INNSE documents for a detailed description of the multiplexed bus; in this chapter, only the hardware signal names are described. The signal abbreviation is the same as used by INNSE, this means that it is not similar to, for example, the Altitude system. In order to integrate the INNSE abbreviation system in the NTT signal system, all Hydrostatic Bearing signals have the prefix HB.
The emergency stop buttons in the building basement are series connected in the HB VME cabinet, and routed from there via two slipring contacts to the building VME cabinet. Each button also generates a computer signal.
NAME | SIGNAL | DESCRIPTION |
AUMHSZO* | DO*1 | Selection of auto mode of operation (f=manual) |
NRDUSZO* | DO*1 | Selection of normal mode (f=degraded) |
STARTAUO* | DO*1 | Start automatic sequence, impulsive signal |
STOPAUO* | DO*1 | Stop automatic sequence, impulsive signal |
STWARMUPO* | DO*1 | Start warm-up sequence, impulsive signal |
COMRESO* | DO*1 | Command reset, impulsive signal (oil 'STOP' command) |
ALRESO* | DO*1 | Alarms reset, impulsive signal |
EMSTOPO | DO*1 | Emergency stop from ESO (Local/Main) |
GESTOPO | DO*1 | General stop from ESO |
ASMOO* | DO*1 | Telescope in motion |
Note: Impulsive signals must be at least 500 msec in length.
NAME | SIGNAL | DESCRIPTION |
SZMHI* | DI*1 | Manual mode selected |
SZTPI* | DI*1 | Test mode selected |
SZAUI* | DI*1 | Automatic mode selected |
SZOPRTI* | DI*1 | Remote mode selected (f=local) |
SZOPNRI* | DI*1 | Normal environment selected (f=degraded) (1=REM , 0=LOCAL) |
MAAUI* | DI*1 | Automatic sequence activated |
MAWBOLI* | DI*1 | Oil warm-up activated |
SZVVRN1I* | DI*1 | Chilled water regulator valve 1 selected |
SZVVRN2I* | DI*1 | Chilled water regulator valve 2 selected |
SZEVPWOLI* | DI*1 | Oil feed command to bearing |
MAMPRC1I* | DI*1 | Oil filtering pump 1 activated |
MAMPRC2I* | DI*1 | Oil filtering pump 2 activated |
MAMPPW1I* | DI*1 | Oil feed pump 1 activated |
MAMPPW2I* | DI*1 | Oil feed pump 2 activated |
WBOLOKI* | DI*1 | Oil adjustment in tolerance |
ALISI* | DI*1 | Immediate alarm (f=normal operation) |
ALRII* | DI*1 | Delayed alarm/ warning (f= normal operation) |
ALMXI* | DI*1 | Multiple alarms/ warnings |
AREMI | DI*1 | Emergency stop (f=normal operation) |
ARGEI | DI*1 | General stop (f=normal operation) |
ARISI | DI*1 | Emergency stop request (f=normal operation) |
NAME | SIGNAL | DESCRIPTION |
ADDRxO* | DO*7 | Address bus, x=6 (MSB) through 0 (see Note 1) |
ADDPARO* | DO*1 | Address bus parity |
ADDSTRO* | DO*1 | Address strobe |
ADDACKI* | DI*1 | Address acknowledge |
ADDPARERI* | DI*1 | Address parity error |
DATAxxI* | DI*16 | Data bus, xx=15 (MSB) through 00 (see Note 2) |
DATAPARLI* | DI*1 | Data bus parity, low byte |
DATAPARHI* | DI*1 | Data bus parity, high byte |
DATASTRI* | DI*1 | Data strobe |
DATAACKO* | DO*1 | Data acknowledge |
Note 1: Software assignment for the address bus is HBADDRESS*,this accesses the whole port (8 bits, of which 6 are used).
Note 2: Software assignment for the data bus is HBDATAHBYTE* and HBDATALBYTE* for the high and low bytes respectively. This accesses one port (8 bits) each.
NAME | SIGNAL | DESCRIPTION |
ESBUBA01I* | DI*1 | Emergency stop button in building basement, 1 |
ESBUBA02I* | DI*1 | Emergency stop button in building basement, 2 |
ESBUBA03I* | DI*1 | Emergency stop button in building basement, 3 |
ESBUBA04I* | DI*1 | Emergency stop button in building basement, 4 |
This signal schedule describes the location of the VME computer signals of the Hydrostatic Bearing. The signals are explained in Section 7.2.
This section provides the information to track each signal from the software driver to the input or output of the VME board. The VME system for the Hydrostatic Bearing contains two digital I/O interface boards.
The signals are connected via flat cable to the Weidmueller multi-termination strips (MTS1 through MTS4). From here, two special cables run to the INNSE opto-coupler box connectors J2 and J4,
The assignment of the signals is such that MTS1 is connected with J4 only; MTS2 and MTS3 are connected with J2 only; MTS4 is spare. From J4, some signals are connected to TS1 (power, emergency). The weather data enters via the RS232 port.
SIGNAL | BOARD | BIT | BIT SIZE | TERMINAL STRIP | ACRO PIN | ACTIVE LEVEL | EXTERNAL WORLD | DESCRIPTION |
ADD0O* | /acro0 | 0 | 1 | MTS1-15 | B32 | LOW | J4-A | address code lsb |
ADD1O* | /acro0 | 1 | 1 | MTS1-13 | B31 | LOW | J4-B | address code |
ADD2O* | /acro0 | 2 | 1 | MTS1-11 | B30 | LOW | J4-C | address code |
ADD3O* | /acro0 | 3 | 1 | MTS1-9 | B29 | LOW | J4-D | address code |
ADD4O* | /acro0 | 4 | 1 | MTS1-7 | B28 | LOW | J4-E | address code |
ADD5O* | /acro0 | 5 | 1 | MTS1-5 | B27 | LOW | J4-F | address code |
ADD6O* | /acro0 | 6 | 1 | MTS1-3 | B26 | LOW | J4-H | address code msb |
ADDPARO* | /acro0 | 7 | 1 | MTS1-1 | B25 | LOW | J4-J | address bus parity bit |
ADDSTRO* | /acro0 | 8 | 1 | MTS1-31 | B24 | LOW | J4-K | address strobe |
DATAACKO* | /acro0 | 9 | 1 | MTS1-29 | B23 | LOW | J4-L | data acknowledge |
AUMHSZO* | /acro0 | 10 | 1 | MTS1-27 | B22 | LOW | J4-M | selection of automatic/ manual |
NRDUSZO* | /acro0 | 11 | 1 | MTS1-25 | B21 | LOW | J4-N | selection of normal/ degraded |
STARTAUO* | /acro0 | 12 | 1 | MTS1-23 | B20 | LOW | J4-P | start automatic sequence (pulse) |
STOPAUO* | /acro0 | 13 | 1 | MTS1-21 | B19 | LOW | J4-R | stop automatic sequence (pulse) |
STWARMUPO* | /acro0 | 14 | 1 | MTS1-19 | B18 | LOW | J4-S | Start warm-up sequence (pulse) |
COMRESO* | /acro0 | 15 | 1 | MTS1-17 | B17 | LOW | J4-T | command reset (pulse) |
ALRESO* | /acro0 | 16 | 1 | MTS1-47 | A32 | LOW | J4-U | alarm reset (pulse) |
EMSTOPO* | /acro0 | 17 | 1 | MTS1-45 | A31 | HIGH | J4-V | emergency stop from LCU |
GESTOPO* | /acro0 | 18 | 1 | MTS1-43 | A30 | HIGH | J4-W | general stop from LCU |
ASMOO* | /acro0 | 19 | 1 | MTS1-41 | A29 | LOW | J4-X | telescope in motion (not used) |
SIGNAL | BOARD | BIT | BIT SIZE | TERMINAL STRIP | ACRO PIN | ACTIVE LEVEL | EXTERNAL WORLD | DESCRIPTION |
HBDATAI* | /acro03 | 2 | 1 | MTS2-16 | C32 | LOW | J2-K | data bus lsb |
HBDATAI* | /acro03 | 3 | 1 | MTS2-14 | C31 | LOW | J2-L | data bus |
HBDATAI* | /acro03 | 4 | 1 | MTS2-12 | C30 | LOW | J2-M | data bus |
HBDATAI* | /acro03 | 5 | 1 | MTS2-10 | C29 | LOW | J2-N | data bus |
HBDATAI* | /acro03 | 6 | 1 | MTS2-8 | C28 | LOW | J2-P | data bus |
HBDATAI* | /acro03 | 7 | 1 | MTS2-6 | C27 | LOW | J2-R | data bus |
HBDATAI* | /acro03 | 8 | 1 | MTS2-4 | C26 | LOW | J2-S | data bus |
HBDATAI* | /acro03 | 9 | 1 | MTS2-2 | C25 | LOW | J2-T | data bus |
HBDATAI* | /acro04 | 0 | 1 | MTS2-32 | C24 | LOW | J2-A | data bus |
HBDATAI* | /acro04 | 1 | 1 | MTS2-30 | C23 | LOW | J2-B | data bus |
HBDATAI* | /acro04 | 2 | 1 | MTS2-28 | C22 | LOW | J2-C | data bus |
HBDATAI* | /acro04 | 3 | 1 | MTS2-26 | C21 | LOW | J2-D | data bus |
HBDATAI* | /acro04 | 4 | 1 | MTS2-24 | C20 | LOW | J2-E | data bus |
HBDATAI* | /acro04 | 5 | 1 | MTS2-22 | C19 | LOW | J2-F | data bus |
HBDATAI* | /acro04 | 6 | 1 | MTS2-20 | C18 | LOW | J2-H | data bus |
HBDATAI* | /acro04 | 7 | 1 | MTS2-18 | C17 | LOW | J2-J | data bus msb |
HBDATAPARLI* | /acro04 | 8 | 1 | MTS2-48 | A1 | LOW | J2-U | data bus parity low byte |
HBDATAPARHI* | /acro04 | 9 | 1 | MTS2-46 | A2 | LOW | J2-V | data bus parity high byte |
HBDATASTRI* | /acro05 | 0 | 1 | MTS2-44 | A3 | LOW | J2-W | data strobe |
HBADDACKI* | /acro05 | 1 | 1 | MTS2-42 | A4 | LOW | J2-X | address acknowledge |
HBADDPAPERI* | /acro05 | 2 | 1 | MTS2-40 | A5 | LOW | J2 | -Yaddress bus parity |
SIGNAL | BOARD | BIT | BIT SIZE | TERMINAL STRIP | ACRO PIN | ACTIVE LEVEL | EXTERNAL WORLD | DESCRIPTION |
HBSZMHI* | /acro1 | 0 | 1 | MTS3-15 | B32 | LOW | J2-Z | !manual mode selected |
HBSZTPI* | /acro1 | 1 | 1 | MTS3-13 | B31 | LOW | J2-a | test mode selected |
HBSZAUI* | /acro1 | 2 | 1 | MTS3-11 | B30 | LOW | J2-b | automatic mode selected |
HBSZOPRTI* | /acro1 | 3 | 1 | MTS3-9 | B29 | LOW | J2-c | remote mode selected |
HBSZOPNRI* | /acro1 | 4 | 1 | MTS3-7 | B28 | LOW | J2-d | normal environment selected |
HBMAAUI* | /acro1 | 5 | 1 | MTS3-5 | B27 | LOW | J2-e | automatic sequence activated |
HBMAWBOLI* | /acro1 | 6 | 1 | MTS3-3 | B26 | LOW | J2-f | oil warm-up activated |
HBSZVVRN1I* | /acro1 | 7 | 1 | MTS3-1 | B25 | LOW | J2-h | chilled water regulator valve 1 selected |
HBSZVVRN2I* | /acro1 | 8 | 1 | MTS3-31 | B24 | LOW | J2-j | chilled water regulator valve 2 selected |
HBSZEVPWOLI* | /acro1 | 9 | 1 | MTS3-29 | B23 | LOW | J2-k | oil feed command to bearing |
HBMAMPRC1I* | /acro1 | 10 | 1 | MTS3-27 | B22 | LOW | J2-m | oil filtering pump 1 activated |
HBMAMPRC2I* | /acro1 | 11 | 1 | MTS3-25 | B21 | LOW | J2-n | oil filtering pump 2 activated |
HBMAMPPW1I* | /acro1 | 12 | 1 | MTS3-23 | B20 | LOW | J2-p | oil feed pump 1 activated |
HBMAMPPW2I | /acro1 | 13 | 1 | MTS3-21 | B19 | LOW | J2-r | oil feed pump 2 activated |
HBWBOLOKI* | /acro1 | 15 | 1 | MTS3-17 | B17 | LOW | J2-t | oil adjustment in tolerance |
HBALISI* | /acro1 | 16 | 1 | MTS3-47 | A32 | LOW | J2-u | immediate alarm |
HBALRII* | /acro1 | 17 | 1 | MTS3-45 | A31 | LOW | J2-v | delayed alarm/warning |
HBALMXI* | /acro1 | 18 | 1 | MTS3-43 | A30 | LOW | J2-w | multiple alarms/warnings |
HBAREMI* | /acro1 | 19 | 1 | MTS3-41 | A29 | HIGH | J2-x | emergency stop |
HBARGEI* | /acro1 | 20 | 1 | MTS3-39 | A28 | HIGH | J2-y | general stop |
HBARISI* | /acro1 | 21 | 1 | MTS3-37 | A27 | HIGH | J2-z | emergency stop request |
SIGNAL | BOARD | BIT | BIT SIZE | TERMINAL STRIP | ACRO PIN | ACTIVE LEVEL | DESCRIPTION |
HBSPARE5O* | /acro1 | 32 | 1 | MTS4-16 | C16 | LOW | INSEremote mode enable(RL5) via TS3-1 and TS3-2 to INSE rack |
HBESBUBA04I* | /acro1 | 44 | 1 | MTS4-24 | C20 | LOW | emergency stop button building 4(RL4) |
HBESBUBA03I* | /acro1 | 45 | 1 | MTS4-22 | C19 | LOW | emergency stop button building 3(RL3) |
HBESBUBA02I* | /acro1 | 46 | 1 | MTS4-20 | C18 | LOW | emergency stop button building 2(RL2) |
HBESBUBA01I* | /acro1 | 47 | 1 | MTS4-18 | C17 | LOW | emergency stop button building 1(RL1) |
Emergency Stop from ESO | TS1-3 | yel/gry | jumpered to TS1-4 |
(relay contact) | TS1-4 | gry/grn | jumpered to TS1-3 |
General Stop from ESO | TS1-1 | brn/blk | jumpered to TS1-2 |
(relay contact) | TS1-2 | wht/blk | jumpered to TS1-1Stop to ESOTS1-5.not used |
(contact opening) | TS1-6 | .not used | Interlock to AZ |
(pressure low) | TS1-7 | brn | AZ interlock via slipring 22 |
(contact opening) | TS1-8 | wht | AZ interlock return via slipring 32 |
Emergency Stop Interlock | TS1-9 | brn | ?to BUEmergency Stop ReturnTS1-10wht?to BU |
Some interconnections on the INNSE opto-coupler box connectors are required to provide the INNSE signal; CKSICC (connector safety).
These connections are not related to any VME signal.
The VME 5V supply is used for the INNSE opto-couplers.
The VME+ and -12V power is used for interfacing the weather data.
Connector Safety
Power
This section refers to the maintenance information for the NTT Hydrostatic Bearing VME System; references to drawings, data sheets and other information are included.
Interfacing of weather data (RS232 link) and the VME supply (+12V and -12V)is via TS2.
TITLE/ SUB-TITLE | SHT NUMBER | LAST UPDATE | DRAWING NUMBER |
HB Interface Schematic Diagram | . | . | 126-10-88CS-E-1602 |
Emergency Stops in Building Basement | . | . | 07-05-90HYBEAR.SCH |
DESCRIPTIONNO. OF SHEETSBurr-Brown Opto-transceiver LDM803INNSE Bearing System Controller.
Separate documentation from: