The building for NTT was delivered by the contractors, complete with all necessary electrical equipment. In order to perform computer control from the VME side, the building control panel has "automatic control" selection switches for the various functions. Note that this "automatic control" means controlled with the VME computer as opposed to push-button control.
This section describes the control interface and an operating procedure. Each building subsystem is described in a separate section.
The following sections give specific information:
The building automatic control is built around a VME system containing an Ethernet interface to communicate with the main computer. The VME system controls the following subsystems:
These subsystems are described separately in the following sections.
Note: The Air condioner is a self supporting unit, provided by the building subcontractor. In case of a malfunction, a checkout at the Air condioner Local Control Unit must be carried out.
The signals in Subsection 4.12.1 explain themselves; two output signals are provided: to inflate or deflate. In addition, two corresponding input signals which sense the status of the bottom seal. The last signal informs the VME computer if the bottom seal function is in automatic selection mode, i.e. can be commanded via the VME computer.
A hardware interlock is provided so that no building rotation is possible when the bottom seal is inflated.
The sequence to inflate is:
After 50 seconds :
For deflating, the sequence is the same, but use the signals BSDEFLO* and BSLSDEFI*.
A similar I/O structure as for the bottom seal applies to the flaps.
The Trivolt power supply has to be adjusted according to the cable length:
The building rotation (called rotation in the following section), is controlled via position sensors between building and azimuth box.
The Control System is in principle a self supporting system, i.e. it does not need any servo loop software. It will be explained in detail in Subsection 4.6.1.
This PI controller is especially designed for the building rotation, and has the following features:
The sensors are Hottinger Baldwin type W50TS combined with an amplifier type MGT 233.0. The two position outputs have a sensitivity of 0.2 V/mm. The PI card inputs have a differential receiver with selectable grounding.
As the measuring amplifier has ground referenced outputs, the ground connection can be left open in the actual system. But during test and integration the jumper must be in one or the other position and a grounding system checkout must be done before the jumper is removed. The sensor tip is replaced with a type that has a rolling ball.
This is an analog computer output to the PI controller: ROPOSOFF????. The scaling is 1 degree/Volt. If the digital signal Apply Position Offset (ROPIAPOO*) is active, ROPOSOFF???? makes it possible to offset the building with respect to the azimuth. This can be necessary in the following cases:
Before the actual PI controller amplifier, a breakout point is provided to implement a filter if necessary. This can be used in order to optimize the open loop performance of the position loop. In the actual system, this possibility is not used.
The PI controller generates an interlock in each of the following cases:
In order to move out of a 3 degree interlock, the following procedure is foreseen:
The building drive system can be enabled and disabled without switching power. This feature makes enabling possible only when it is required. This enable can be done in two ways:
Both possibilities are "wire OR-ed" in the hardware. This means that one of the two is sufficient to assert RODRENABO.
The PI card generates the building drive enable in each of the following cases (OR function):
In practice, these two settings are not independent because of the fact that only a relatively low integral gain can be allowed. A higher integral gain will cause limit cycles. The switching level is therefore determined by the speed command.
When the drive system is enabled, the rotation system tries to decrease the position error to 0 and the system is kept enabled as long as there is a certain minimum speed.
If both position error and speed are within the limit, then the system is kept enabled during an adjustable time, which prevents too fast enable/disable switching. This delay is set to 7 seconds.
During test and integration, jumper J5 can be inserted on the PI card to enable the building continuously, i.e. independent of position error or speed.
Asserting of RODRENABO also enables the building drive. This is an OR function with the PI controller signal. This signal makes it possible to enable the building drive continuously if this is required for any reason, e.g. fast and stepwise motions.
Note, however, that the position PI controller provides only an output signal to the rotation velocity loop if at least one of the conditions, mentioned in the previous paragraph, is fulfilled. If not, the velocity reference is zero.
The velocity reference is fed to the building electronic racks via an isolation amplifier. This is done to have a complete galvanic isolation between building drive systems and VME computer.
Most of the important items concerning operating the building system have already been explained in the previous paragraphs. More is described in the next paragraph.
A certain sequence of commands and checks has to be done to switch on the building rotation drive system:
To switch the rotation system off:
The description above and the electrical drawings and data sheets provide the basic information for maintenance. As a help, a list of scaling values and the adjustment procedure for the position PI controller is described below.
Interchanging of the PI controller board for a spare one means also that the position loop has to be adjusted. The procedure is as follows:
Notes:
The signals in Subsection 4.12.7 explain themselves; two output signals are provided: to open or close. In addition, two corresponding input signals which sense the status of the door. The last signal informs the VME computer if the door function is in automatic selection mode, i.e. can be commanded via the VME computer.
Refer to Subsection 4.12.8. The implementation of the slit shutter signals is done as follows: one bit is provided to switch the 380V power. Two bits are provided which need an impulsive signal in order to start and to stop the motion. The direction is controlled by another bit. The length of the impulsive signals has to be 3 seconds.
Refer to Subsection 4.12.9. The implementation of the windscreen signals is as follows: one bit is provided to switch the 380V power. Two bits are provided which need an impulsive signal in order to start and to stop the motion. The direction is controlled by another bit. The length of the impulsive signal has to be 100 milliseconds. Another signal is provided which senses if the chain of the windscreen is broken: WSLSCHI*. If this signal is asserted, no operation is possible.
The absolute encoder is manufactured by Siemens. A similar type is also used for the windscreen and the rotation. From the control side, two possible different types can be implemented:
Together with a choice of gear reduction, a good scaling value can be chosen. The absolute encoder has BCD outputs. Digit 3 is not used for the 1000 counts type. The encoder type V23463-K0901-D315 (100.000 counts, 100 turn) can be used, but the fifth decade is not connected.
Because of the long distance between encoder and VME rack, a line driver/receiver link is designed. The line driver and the power supply are located close to the encoder. The receiver is mounted in the VME rack.
In order to eliminate electrical interference problems, this link has its own power supply (which also powers the line receiver) and has Opto-couplers between the receiver IC's and the VME inputs.
Refer to Subsection 4.12.2. The emergency stop buttons, installed in the rotating part of the building, are routed to the building VME rack. There is a computer signal generated for each switch, using 1 contact of the button. The other contact of each button is put in series and forms a part of the Emergency Stop push-button chain. For a complete picture of this chain, refer to Subsection 1.5.2.
Refer to Subsection 4.12.11. The signal 380VPFI* indicates a power failure in the building main power distribution. It has been implemented to make it possible for the software to detect power failures. Neither the VME nor the TCS Workstation suffer from a power failure because they are connected to the un-interruptable power supply.
The software action on a power failure has to be: stop driving any building function immediately.
The signals in the building subsystem are divided into the following groups which indicate where the signals originate (inputs to the computer), or where they have to be routed (outputs from the computer).
4.12.1 Bottom Seal Signals
NAME | TYPE | DESCRIPTION |
BSINFLO* | DO*1 | Bottom Seal inflate command |
BSDEFLO* | DO*1 | Bottom Seal deflate command |
BSLSINFI* | DI*1 | Bottom Seal Limit Switch, seal inflated |
BSLSDEFI* | DI*1 | Bottom Seal Limit Switch, seal deflated |
BSAUTSELI* | DI*1 | Bottom Seal, automatic control selected |
The switches detailed below are mounted in the rotating part of the building and have no direct connection with any other VME computer; the switches are numbered as shown.
NAME | TYPE | DESCRIPTION |
ESBUCO05I* | DI*1 | Building Control (tech. service. room) switch |
ESCORO06I* | DI*1 | Control Room switch (6) |
ESCORO07I* | DI*1 | Control Room switch (7) |
ESEMRO08I* | DI*1 | EMMI Room (big inst. room) switch |
ESWSRO09I* | DI*1 | Windscreen area (9) switch |
ESWSRO10I* | DI*1 | Windscreen area (10) switch |
ESIRRO11I* | DI*1 | IRSPEC Room (small. inst. room) switch |
ESTESD12I* | DI*1 | Telescope Room, sliding door side switch |
The flaps have a Siemens absolute encoder with BCD outputs. The selected type will have three or four digits; the hardware can accommodate either type.
NAME | TYPE | DESCRIPTION |
FLOPENO* | DO*1 | Flaps open command |
FLCLOSEO* | DO*1 | Flaps close command |
FLLSOPI* | DI*1 | Flaps opened limit detected |
FLLSCLI* | DI*1 | Flaps closed limit detected |
FLAUTSELI* | DI*1 | Flaps automatic control selected |
Anemometer on Top of Building
NAME | TYPE | DESCRIPTION |
WIHMAGI | AI*2 | Horizontal magnitude |
WIREFI | AI*3 | Reference value 2.5V |
WIVVELI | AI*4 | Vertical velocity |
WIDIRI | AI*5 | Wind direction |
Anemometer on Telescope Top Ring
NAME | TYPE | DESCRIPTION |
TWIHMAGI | AI*6 | Horizontal magnitude |
TWIVVELI | AI*9 | Vertical velocity |
TWIREFI | AI*8 | Maximal gust (Rafaga) |
TWIDIRI | AI*7 | Wind direction |
CANNON "D" CONNECTOR.
SIGNAL | PIN | COLOUR | T. STRIP | NAME | REMARKS |
out0 | 36 | yellow | . | ROPOSOFF? | . |
ret0 | 17 | green | . | . | gnd |
out1 | 37 | gray/pink | . | . | . |
ret1 | 16 | blue/red | . | . | gnd |
in04 | 6 | brown/gray | . | WIVVEL? | . |
ret04 | 14 | wh./gr. | . | . | gnd |
in02 | 7 | brn/blu | . | WIHMAG? | . |
ret02 | 15 | wh/blu | . | . | gnd |
in03 | 21 | gry | . | WIREF? | . |
ret03 | 29 | pnk | . | . | gnd |
. in01 | 23 | vio | . | ROPOSERRI | . |
ret01 | 31 | blk | . | . | gnd |
in05 | 22 | brn | . | WIDIR? | . |
ret05 | 30 | wh | . | . | gnd |
in00 | 5 | red | . | ROVREFI | . |
ret00 | 13 | blu | . | . | gnd |
in11 | 2 | yel | . | . | . |
ret11 | 10 | grn | . | . | gnd |
in13 | 3 | brn/pnk | . | . | . |
ret13 | 11 | wh/brn | . | . | gnd |
in09 | 4 | brn | 34 | TWIVVEL? | . |
ret09 | 12 | wh | . | . | gnd |
in10 | 26 | brn/red | . | . | . |
ret10 | 34 | wh/red | . | . | gnd |
in12 | 25 | brn/grn | . | . | . |
ret12 | 33 | wh/grn | . | . | gnd |
in06 | 8 | brn/yel | 25 | TWIHMAG? | . |
ret06 | 16 | wh/yel | . | . | gnd |
in07 | 20 | yel | 28 | TWIDIR? | . |
ret07 | 28 | grn | . | . | gnd |
in08 | 24 | brn | 31 | TWIGUST? | . |
ret08 | 32 | wh | . | . | gnd |
The rotation of the building is controlled by position sensors which sense the angle difference between building and azimuth. This is done in an analog way, so there is a position PI controller in hardware. The hardware enables the building drive signal (RODRENAB) if:
The software can also drive the signal RODRENAB at any time. So, there is an OR function implemented for this signal. For more information about the rotation system, refer to Section 4.6.
NAME | TYPE | DESCRIPTION |
ROVREFI | AI*12 | Velocity reference to building drive (test-point for software) |
ROPOSERRI | AI*12 | Building position error (test-point for software) |
ROPOSOFFO | AO*12 | Building position offset |
RODRENABO* | DO*1 | Building drive enable |
ROILENABO* | DO*1 | Building interlock enable; this signal switches on the power to the amplifier |
ROPIAPOO* | DO*1 | Building PI Controller, apply position offset - i.e. feed signal ROPOSOFF to PI Controller |
ROPIRSTO* | DO*1 | Building PI Controller reset |
ROWARNO* | DO*1 | Building rotation warning lamps ON |
ROIL3DI* | DI*1 | Building interlock, 3 degrees pos. or neg. limit detected |
ROILPII* | DI*1 | Building PI Controller interlock |
ROPADISI* | DI*1 | Building drive power amplifier disabled |
ROAUTSELI* | DI*1 | Building drive automatic control selected |
Take adequate precautions to warn personnel when the door is operated under remote control.
NAME | TYPE | DESCRIPTION |
SDOPENO* | DO*1 | Sliding door open command |
SDCLOSEO* | DO*1 | Sliding door close command |
SDLSOPI* | DI*1 | Sliding door opened limit detected |
SDLSCLI | DI*1 | Sliding door closed limit detected |
SDAUTSELI* | DI*1 | Sliding door automatic control selected |
NAME | TYPE | DESCRIPTION |
SSSTRTO* | DO*1 | Slit Shutter start command (impulse signal) |
SSSTOPO* | DO*1 | Slit Shutter stop command (impulse signal) |
SSCLOSEO* | DO*1 | Slit Shutter close direction signal |
SSPWONO* | DO*1 | Slit Shutter power on |
SSLSOPI* | DI*1 | Slit Shutter opened limit detected |
SSLSCLI* | DI*1 | Slit Shutter closed limit detected |
SSAUTSELI* | DI*1 | Slit Shutter automatic control selected |
The Windscreen has a Siemens absolute encoder with BCD outputs. The selected type have 4 digits.
NAME | TYPE | DESCRIPTION |
WSSTRTO* | DO*1 | Windscreen start command (impulse signal) |
WSSTOPO* | DO*1 | Windscreen stop command (impulse signal) |
WSUPO* | DO*1 | Windscreen up direction select |
WSPWONO* | DO*1 | Windscreen power on |
WSLSUPI* | DI*1 | Windscreen up limit detected |
WSLSDNI* | DI*1 | Windscreen down limit detected |
WSLSCHI* | DI*1 | Windscreen chain broken detected |
WSAUTSELI* | DI*1 | Windscreen automatic control selected |
WSAENCI | DI*8 | Windscreen Absolute Encoder |
The interlock signals which refer to a certain building subsystem are explained in the appropriate chapter. Note that other emergency stop signals, which were installed later, are described in Subsection 4.12.2 and have the abbreviation ESxxx.
NAME | TYPE | DESCRIPTION |
ILEMSTO1I* | DI*1 | Building Emergency Stop button pressed |
ILEMCOMI* | DI*1 | Any Emergency Stop button pressed |
NAME | TYPE | DESCRIPTION |
380VPFI* | DI*1 | Building 380V phase failure |
This signal schedule describes the location for the VME computer signals of the building. The signals are explained in Section 4.12. This section provides the information to track each signal from the software driver to the input or output of the VME board, and to the building racks.
The VME system for the building contains two Digital I/O interface boards, and one Analog I/O board.
The digital signals are connected via dedicated cable to the Weidmueller Multi-termination strips MTS1 and MT2. From here, the VME outputs to the building racks run via Optotriacs using MTS1. The VME inputs from the building racks are connected via relays, using MTS2. The work station encoder signals are connected via cable from back connector of the encoder Opto-coupler Eurocard rack. This is done without using Weidmueller Multi-termination strips. The analog inputs and outputs are connected to TS3.
SIGNAL | BOARD | BIT | BIT SIZE | TERM. STRIP | ACRO PIN | ACT. LEVEL | EXT. WORLD | DESCRIPTION |
SSPWONO* | /acro0 | 0 | 1 | MTS1-15 | B32 | LOW | OPT#16 | slit shutter power on |
SSCLOSEO* | /acro0 | 1 | 1 | MTS1-13 | B31 | LOW | OPT#6 | slit shutter move direction |
SSSTRTO* | /acro0 | 2 | 1 | MTS1-11 | B30 | LOW | OPT#5 | start move slit shutter |
SSSTOPO* | /acro0 | 3 | 1 | MTS1-9 | B29 | LOW | OPT#4 | stop move slit shutter |
WSPWONO* | /acro0 | 4 | 1 | MTS1-7 | B28 | LOW | OPT#15 | power on windscreen |
WSUPO* | /acro0 | 5 | 1 | MTS1-5 | B27 | LOW | OPT#3 | windscreen move direction |
WSSTRTO* | /acro0 | 6 | 1 | MTS1-3 | B26 | LOW | OPT#2 | start move windscreen |
WSSTOPO* | /acro0 | 7 | 1 | MTS1-1 | B25 | LOW | OPT#1 | stop move windscreen |
FLCLOSEO* | /acro0 | 8 | 1 | MTS1-31 | B24 | LOW | OPT#10 | close flaps |
FLOPENO* | /acro0 | 9 | 1 | MTS1-29 | B23 | LOW | OPT#9 | open flaps |
ROWARNO* | /acro0 | 11 | 1 | MTS1-25 | B21 | LOW | OPT#17 | warning lamps on (not used) |
ROPIRSTO* | /acro0 | 12 | 1 | MTS1-23 | B20 | LOW | TS2-1 PI reset | PI controller reset (not used) |
ROPIAPOO* | /acro0 | 13 | 1 | MTS1-21 | B19 | LOW | TS2-3 to PI | apply position offset (not used) |
ROILENABO* | /acro0 | 14 | 1 | MTS1-19 | B18 | LOW | OC1-A2 | power on building rotation |
RODRENABO* | /acro0 | 15 | 1 | MTS1-17 | B17 | LOW | TS5-7 to PI | building drive enable |
BSDEFLO* | /acro0 | 18 | 1 | MTS1-43 | A30 | LOW | OPT#14 | deflate bottom seal |
BSINFLO* | /acro0 | 19 | 1 | MTS1-41 | A29 | LOW | OPT#13 | inflate bottom seal |
SDOPENO* | /acro0 | 22 | 1 | MTS1-35 | A26 | LOW | OPT#12 | close sliding door |
SDCLOSEO* | /acro0 | 23 | 1 | MTS1-33 | A25 | LOW | OPT#11 | open sliding door |
ESTESD12I* | /acro0 | 24 | 1 | MTS1-63 | A24 | LOW | Relay24 | emergency button telescope room |
ESIRRO11I* | /acro0 | 26 | 1 | MTS1-61 | A22 | LOW | Relay25 | emergency button IR room |
ESWSRO10I* | /acro0 | 28 | 1 | MTS1-59 | A20 | LOW | Relay26 | emergency button windscreen area |
SIGNAL | BOARD | BIT | BIT SIZE | TERM. STRIP | ACRO PIN | ACT. LEVEL | EXT. WORLD | DESCRIPTION |
SSAUTSELI* | /acro0 | 33 | 1 | MTS2-14 | C31 | LOW | Relay7 | slit shutter automatic control selected |
SSLSCLI* | /acro0 | 34 | 1 | MTS2-12 | C30 | LOW | Relay6 | slit shutter close limit switch |
SSLSOPI* | /acro0 | 35 | 1 | MTS2-10 | C29 | LOW | Relay5 | slit shutter open limit switch |
WSAUTSELI* | /acro0 | 36 | 1 | MTS2-8 | C28 | LOW | Relay4 | windscreen automatic control selected |
SWLSCHI* | /acro0 | 37 | 1 | MTS2-6 | C27 | LOW | Relay3 | windscreen chain broken limit switch |
WSLSDNI* | /acro0 | 38 | 1 | MTS2-4 | C26 | LOW | Relay2 | windscreen down limit switch |
WSLSUPI* | /acro0 | 39 | 1 | MTS2-2 | C25 | LOW | Relay1 | windscreen up limit switch |
FLAUTSELI* | /acro0 | 40 | 1 | MTS2-32 | C24 | LOW | Relay13 | flaps automatic control selected |
FLLSCLI* | /acro0 | 41 | 1 | MTS2-30 | C23 | LOW | Relay12 | flaps close limit switch |
FLLSOPI* | /acro0 | 42 | 1 | MTS2-28 | C22 | LOW | Relay11 | flaps open limit switch |
ROILPI* | /acro0 | 44 | 1 | MTS2-24 | C20 | LOW | . | building PI controller interlock |
ROAUSELI* | /acro0 | 45 | 1 | MTS2-22 | C19 | LOW | Relay10 | building automatic control selected |
ROPADISI* | /acro0 | 46 | 1 | MTS2-20 | C18 | LOW | . | building power amplifier disabled |
ROIL3DI* | /acro0 | 47 | 1 | MTS2-18 | C17 | LOW | Relay8 | three degree interlock detected |
BSAUTSELI* | /acro0 | 49 | 1 | MTS2-46 | A2 | LOW | Relay19 | bottom seal automatic control selected |
BSLSDEFI* | /acro0 | 50 | 1 | MTS2-44 | A3 | LOW | Relay18 | bottom seal deflated limit switch |
BSLSINFI* | /acro0 | 51 | 1 | MTS2-42 | A4 | LOW | Relay17 | bottom seal inflated limit switch |
SDAUTSELI* | /acro0 | 53 | 1 | MTS2-38 | A6 | LOW | Relay16 | sliding door automatic control selected |
SDLSCLI* | /acro0 | 54 | 1 | MTS2-36 | A7 | LOW | Relay15 | sliding door close limit switch |
SCLSOPI* | /acro0 | 55 | 1 | MTS2-34 | A8 | LOW | Relay14 | sliding door open limit switch |
ESEMRO08I* | /acro0 | 56 | 1 | MTS1-55 | A9 | LOW | Relay28 | emergency button EMMI room |
ESCORO07I* | /acro0 | 57 | 1 | MTS1-53 | A10 | LOW | Relay29 | emergency button control room |
ESWSRO09I* | /acro0 | 58 | 1 | MTS2-56 | A11 | LOW | Relay27 | emergency button windscreen area |
380VPFI* | /acro0 | 59 | 1 | MTS2-54 | A12 | LOW | Relay23 | building 380V phase failure |
ESCORO06I* | /acro0 | 60 | 1 | MTS1-51 | A13 | LOW | Relay30 | emergency button control room |
ESBUCO05I* | /acro0 | 61 | 1 | MTS1-49 | A14 | LOW | Relay31 | emergency button building control room |
ILEMCOMI* | /acro0 | 62 | 1 | MTS2-52 | A15 | LOW | . | any emergency button |
ILEMSTO01I* | /acro0 | 63 | 1 | MTS2-50 | A16 | LOW | . | building emergency stop button |
SIGNAL | BOARD | BIT | BIT SIZE | TERMINAL STRIP | ACRO PIN | ACTIVE LEVEL | DESCRIPTION |
WSAENCI | /acro0 | 0 | 1 | encoder | B32 | HIGH | windscreen absolute encoder |
WSAENCI | /acro0 | 1 | 1 | encoder | B31 | HIGH | windscreen absolute encoder |
WSAENCI | /acro0 | 2 | 1 | encoder | B30 | HIGH | windscreen absolute encoder |
WSAENCI | /acro0 | 3 | 1 | encoder | B29 | HIGH | windscreen absolute encoder |
WSAENCI | /acro0 | 4 | 1 | encoder | B28 | HIGH | windscreen absolute encoder |
WSAENCI | /acro0 | 5 | 1 | encoder | B27 | HIGH | windscreen absolute encoder |
WSAENCI | /acro0 | 6 | 1 | encoder | B26 | HIGH | windscreen absolute encoder |
WSAENCI | /acro0 | 7 | 1 | encoder | B25 | HIGH | windscreen absolute encoder |
WSAENCI | /acro0 | 8 | 1 | encoder | B24 | HIGH | windscreen absolute encoder |
WSAENCI | /acro0 | 9 | 1 | encoder | B23 | HIGH | windscreen absolute encoder |
WSAENCI | /acro0 | 10 | 1 | encoder | B22 | HIGH | windscreen absolute encoder |
WSAENCI | /acro0 | 11 | 1 | encoder | B21 | HIGH | windscreen absolute encoder |
WSAENCI | /acro0 | 12 | 1 | encoder | B20 | HIGH | windscreen absolute encoder |
WSAENCI | /acro0 | 13 | 1 | encoder | B19 | HIGH | windscreen absolute encoder |
WSAENCI | /acro0 | 14 | 1 | encoder | B18 | HIGH | windscreen absolute encoder |
WSAENCI | /acro0 | 15 | 1 | encoder | B17 | HIGH | windscreen absolute encoder |
SIGNAL | BOARD | CHANNEL | TERMINAL STRIP | AIO PIN | DESCRIPTION |
ROPOSOFFO | /aio0 | OUT-0 | TS3-1,2,3 | A31-C31 | building position offset (not used) |
ROVREFI | /aio0 | IN-0 | TS3-7,8,9 | A1-C1 | velocity reference |
ROPOSERRI | /aio0 | IN-1 | TS3-10,11,12 | A3-C3 | building position error |
SIGNAL | I/O | LOCATION |
ACRS232 | RS232 | Connected to RS232 interface of VME CPU |
VME BOARD | JUMPER SETTING | STATE | FUNCTION |
ACRO 9481 | J1, J3, J5, J7 | Installed | Enables internal pull-up to +5V of the I/O lines |
J2, J4, J6, J8 | Installed | Enable internal threshold reference of the input | |
J17 | Base address: | Base address: | |
board 1; 5-6 installed | ffff1000 hex (/acro0) | ||
board 2; 1-2 and 5-6 installed | ffff1400 hex (/acro1) | ||
J19 | Installed | Short supervisory and non-privileged access | |
J20 | Omitted | SYSFAIL is not asserted after reset | |
VMIC, VMIVME-3111, analog I/O | Default setting is: analog inputs; 16 differential, -10 to +10V | ||
analog outputs; single-ended, -10 to +10V | |||
J1 | Installed | Ground P3 return | |
J2 | Installed | Ground P3 sense | |
J3 | Omitted | 5V full scale input | |
J4 | 1-1 installed | Bipolar analog inputs | |
J5 | 2-3 installed | Auto input gain adjust | |
J6 | Omitted | Unipolar analog inputs not enabled | |
J7, J8 | Omitted | Output test is validated | |
J9, J10, J11 | Omitted | P3 inputs enabled | |
J12 | 1-2 installed | Bipolar analog outputs | |
J13 | Omitted | 20V full scale output range | |
J15 | 1-2 installed | 20V full scale input range | |
J17 to J24 | Omitted | Differential input | |
J27 to J34 | Omitted | Differential input | |
J25 | Omitted | 2.5Vdc reference unused | |
J26 | Installed | 10Vdc reference used | |
J35 | Installed | Ground P2 sense | |
J36, J37 | Base address: | Base address: | |
board 1; J36: 0, 1, 2, 3, 6 and 7 installed | ffff30000 hex (/aio0) | ||
J37: 0, 1 and 2 installed | |||
J37-3 | Omitted | short non-privileged access | |
J38 | 2-3 installed | Auto input zero adjust | |
J39 | Installed | Ground analog outputs return | |
J40 | Omitted | 5Vdc reference unused | |
J41 | Omitted | Ext. trig not connected to P2 ground sense | |
J42 | 1-2 installed | Ext. trig rt. connected to P2 ground sense |
This section lists maintenance information for the NTT building VME rack; also included is a List of Drawings and Data Sheets.
A special sheet is added in the drawings which shows the schematic diagram of the interlock chain in relation to the azimuth interlock and the emergency stop chain.
The interfacing to the building power racks has been designed to ensure complete galvanic isolation between VME rack and power racks. This is done to avoid interference from the thyristor power amplifiers.
Care must be taken during maintenance to avoid any galvanic connection between the two systems via cable shields etc. Treat the velocity reference to the building rotation power amplifier with special care when taking measurements etc.
A special cable duct in the VME rack has been mounted in order to guide the cables to the building power racks with a minimum of interference to the VME computer.
TITLE/ SUB-TITLE | SHT NUMBER | LAST UPDATE | DRAWING NUMBER |
Building Position PI Controller | . | . | CS-P-1495 |
- Schematic Diagram (Sht 1) | 1 | 26-06-88 | . |
- Schematic Diagram (Sht 2) | 2 | 30-06-88 | . |
- PCB Layout | . | . | CS-P-1495A |
Isolation Amplifier | . | . | CS-P-1494 |
- Schematic Diagram | . | 25-07-88 | . |
- PCB Layout | . | . | CS-P-1494A |
Building Control VME Rack Schematic Diagram | . | . | CS-E-1525 |
- Interlock Chain | 1 | 27-04-89 | . |
- Digital I/O | 2 | 18-05-88 | . |
Building Control VME Rack Wiring Diagram | . | . | CS-E-1526 |
- Relay Inputs Part 1 | 3 | 14-03-90 | . |
- Relay Inputs Part 2 | 4 | 14-03-90 | . |
- Position PI Card Controller | 5 | 14-03-90 | . |
- VME Analog I/O Cable | 6 | 14-03-90 | . |
- Interlock Chain | 7 | 14-03-90 | . |
- Miscellaneous Signals | 8 | 14-03-90 | . |
- Layout of Rack Front | 9 | 14-03-90 | . |
- Layout of Rack rear | 10 | 14-03-90 | . |
- Emergency Stop Switches | 11 | 07-05-90 | . |
Building Control VME Rack, Encoder | . | . | CS-E-1540 |
- Schematic Diagram | 1 | 14-03-90 | . |
- Cabling Diagram | 2 | 02-04-89 | . |
- Line Driver, Schematic Diagram | 3 | 07-07-88 | . |
- Line Receiver, Schematic Diagram | 4 | 13-03-90 | . |
- Line Driver, PCB Layout | . | . | CS-P-1516A |
- Line Receiver, PCB Layout | . | . | CS-P-1517A |
Slit Shutter Speed Guard Circuit (Sht 1) | 1 | . | . |
Slit Shutter Speed Guard Circuit (Sht 2) | 2 | . | . |
Slit Shutter Speed Guard Board | . | . | . |
DESCRIPTION | NO. OF SHEETS |
Burr-Brown Opto-transceiver LDM80 | 2 |
Siemens Absolute Encoders | 6 |
Burr-Brown Isolation Amplifier 3650 | 8 |
Burr-Brown DC/ DC Converter PWR 317 | 2 |
Hottinger Baldwin Position Sensor W50TS | 11 |
Hottinger Baldwin Measuring Amplifier MGT 233.0 | 11 |