Bearing System Controller
(Chp7 Section 7.4 NTT Bearing System Control)
HOME | INDEX | SEARCH | HELP | NEWS |
FLHORN (E4.2)
TUHORN (input an)
RGHORN1 and RGHORN2 (output an)
SWRGH01 (E4.0)
SWRGH02 (E4.1)
LMOLRC (E4.5)
LZOLRC1 (E4.3)
LZOLRC2 (E4.4)
SWASFT1 (E4.6)
SWASFT2 (E4.7)
SWABFT1 (E5.0)
SWABFT2 (E5.1)
SWMPRC1 (E5.6)
SWMPRC2 (E5.7)
MPRCOL1 (A9.2)
MPRCOL2 (A9.3)
SWABFT3 (E5.4)
SWABFT4 (E5.5)
SWMDFT3 (E5.2)
SWMDFT4 (E5.3)
FLOLFT (E6.5)
LZOLFT (E6.4)
to feed hydrostatic pads circuit:
DISABLES immediately pumps and oil delivery to hydrostatic system of azimuth axis and STOPS azimuth axis feed motion.
TMOLFT (E7.0)
TUOLCL1 and TUOLCL2 (input an)
SWMPPW1 (E6.6)
SWMPPW2 (E6.7)
MPPWOL1 (A9.4)
MPPWOL2 (A9.5)
(SWMPPW1 * SWMPPW2 = 1).
PSMNOL1 (E6.0)
PSMNOL2 (E6.1)
STOPS immediately the motion of the azimuth axis and REQUESTS action by operator.
EVSCOLID (A9.7)
EVPWOLID (A9.6)
Solenoid EVPWOLID can be energized in AUTOMATIC CYCLE only when the temperature of the oil for the hydrostatic circuit has reached the value programmed from the BSC control system.
In MANUAL OPERATION, test mode, the solenoid EVPWOLID can be energized from the Local Control Panel, and therefore the motion of the azimuth axis can be enabled even if the oil temperature has not reached the programmed value.
PSMNOLID (E6.3)
TFPROLID (input an)
PSMSOLID (E6.2)
Local Control Panel (LCP) represents the local interface of the operator to control and monitor the operations of the Bearing Control System (BCS) of the ESO NEW TECHNOLOGY TELESCOPE (NTT).
LCP is a control panel located on the front door of the electrical cabinet housing the Programmable Logic Control (PLC), as per dwg.Z.0000.70374.
The control panel includes selector switches, pushbuttons, lamps and displays to select the operational modes of the BSC, to command locally, in manual mode, the controls of the hydraulic sytem and of the system to control the oil temperature and to monitor alarms.
LCP includes the following:
SLON (E0.0)/ SLOF (E0.1) & LPON (A0.1)
SLOPLC (E0.2)/ SLOPRT (E0.3) & LPOPLC (A0.1)/ LPOPRT (A0.2)
SLMH (E0.4)/ SLTP (E0.5)/ SLAU (E0.6) & LPMH (A0.3)/ LPTP (A0.4)/ LPAU (A0.5)
MANUAL: | the operator can command pumps start and stop, and he can control operations from the panel. All logic interlocks and the controls for the correct operations of the system are active. |
TEST | the operator has full command of the controls. Only the safety interlocks are active, not to damage the sytem. |
AUTOMATIC | "macro" commands are enabled by the operator from LCP which activate automatic sequences of operations. BSC performs, in AUTOMATIC mode, as controlled by the computer, but the sequences commands are set by the operator. |
SLOPNR (E0.7)/ SLOPDU (E1.0) & LPOPNR (A0.6)/ LPOPDU (A0.7)
The controls and the commands listed under point 1 are accessible under a transparent protective window, key locked, to avoid unauthorized access to the controls.
PUMAAU (E1.1) & LPMAAU (A1.0)
PUSHBUTTON with green LAMP: START AUTOMATIC OPERATION.
Green light blinks if, after a start command, automatic cycle cannot start due
to faulty or missing consents, which are monitored by lamps and displays.
Green light stays on if, after a start command, automatic cycle starts correctly.
PUARAU (E1.2)
PUMAWBOL (E1.3) & LPWBOL (A1.1)
PUARWBOL (E1.4)
SLVVRN1 (E1.5) and SLVVRN2 (E1.6)
LPVVRN1 (A1.2) and LPVVRN2 (A1.3)
SLEVPWOL (E1.7) and SLEVSCOL (E2.0)
LPEVPWOL (A1.4) and LPEVSCOL (A1.5)
Selector Switch SLEVPWOL in enabled only in TEST MODE.
PHRFVVHO (input an)
PHSATURF (input an)
LPSZPH (A1.6)
OIL FEED CIRCUIT TO HYDROSTATIC PADS
PUMAPW1 (E2.5) with LPMAPW1 (A2.1)
PUARPW1 (E2.6)
PUMAPW2 (E2.7) with LPMAPW2 (A2.2)
PUARPW2 (E3.0)
OIL REFRIGERATION AND FILTERING CIRCUIT
PUMARC1 (E2.1) with LPMARC1 (A1.7)
PUARRC1 (E2.2)
PUMARC2 (E2.3) with LPMARC2 (A2.0)
PUARRC2 (E2.4)
Red Pushbutton: STOP OIL FILTERING PUMP (2) OPERATION.
OIL FEED CIRCUIT TO HYDROSTATIC PADS
LPTMOLFT (A8.1)
LPLZOLFT (A8.0)
LPPSMN1 (A8.2)
LPPSMN2 (A8.3)
LPPSMSOL (A8.4)
OIL REFRIGERATION AND FILTERING CIRCUIT
LPASFT1 (A2.3)
LPIOFT1 (A2.4)
LPASFT2 (A2.5)
LPIOFT2 (A2.6)
LPMDFT3 (A2.7)
LPIOFT3 (A3.0)
LPMDFT4 (A3.1)
LPIOFT4 (A3.2)
LPLZOLRC (A3.7)
LPLMOLRC (A3.6)
LPFLOLFT (A3.5)
LPFLHORN (A3.4)
LPTMHORN (A3.3)
VZAL
LPVIAL
PURPAL (E3.7)
PURPSIAL (E3.6)
The Display VZAL can memorize up to 16 messages at the same time, they are
transmitted serially from PLC.
The numeric section (2 digits) displays the number of messages present at
the same time.
Yellow Pushbutton, included in the display, scans the messages and displays
them in order of there priority: the priority is defined by the code associated
to the message.
VZOLID
VZRFVVHO
VZTURF
VZRVTU
PUSZ-ST (E14.6) with LPSZ-ST (A10.0)
PUSZ-RT (E14.6) with LPSZ-RT (A10.1)
PUSZ-PT (E15.0) with LPSZ-PT (A10.2)
PUSZ-TT (E15.1) with LPSZ-TT (A10.3)
PUSZ-WT (E15.2) with LPSZ-WT (A10.4)
PUSZTU1 (E15.3) with LPSTZU1 (A11.0)
PUSZTU2 (E15.4) with LPSTZU2 (A11.1)
PUSZTU3 (E15.6) with LPSTZU3 (A11.2)
PUSZTU4 (E15.6) with LPSTZU4 (A11.3)
PUSZTUMI (E15.7) with LPSTZUMI (A11.4)
The Pushbuttons above listed are used to select the area related to the
measure (STMS, RTMS, PTMS, TTMS, WTMS) and related temperature sensor or the
average value of the temperatures (T1, T2, T3, T4, TM).
The white light related to the pressed pushbutton goes on. When display of
temperature average (TM) is selected, all lights related to the sensors which
concur to the computation of the temperature average go on.
PUTPLP (E3.5)
PUAREM (E11.4)
PUARGE (E11.5)
SISGAL (A8.6)
LPEMCU (A8.5)
LPAREM
ESO COMPUTER and SIMATIC PLC have the following information interchange:
1) Operation mode selections and commands from ESO COMPUTER to PLC
2) Operation mode selections and commands from PLC to ESO COMPUTER
3) Status signals related to Bearing System Controller (BSC) and Temperature
Measuring System (TMS) from PLC to ESO COMPUTER
4) Alarm and warning signals related to BSC and TMS from PLC to ESO COMPUTER
5) Measurement and reference analog signals from PLC to ESO COMPUTER
The groups of signals 1 and 2 are exchanged in parallel using one I/O logic interface for each signal.
To exchange the signals concerning groups 3, 4 and 5 a multiplexed parallel transmission system used, consisting of 16 lines for DATA and 7 lines for ADDRESS, as shown in figure 1 in which is described the complete functional connection between ESO COMPUTER and PLC.
Before describing the hardware interface and the multiplexed parallel transmission protocol, the groups of interface signals are listed below.
AU/MHSZ (E13.2)
NR/DUSZ (E13.3)
STARTAU (E13.4)
STOPAU (E13.5)
STWARMUP (E13.6)
COMREST (E13.7)
ALRESET (E14.0)
EMSTOPU (E14.1)
GESTOP (E14.2)
ASMO (E14.3)
The impulsive signals from ESO COMPUTER must be at least 500msec long.
SZMH (A16.0)
SZTP (A16.1)
SZAU (A16.2)
SZOPRT (A16.3)
SZOPNR (A16.4)
MAAU (A16.5)
MAWBOL (A16.6)
SZVVRN1 (A16.7)
SZVVRN2 (A17.0)
SZEVPWOL (A17.1)
MAMPRC1 (A17.2)
MAMPRC2 (A17.3)
MAMPPW1 (A17.4)
MAMPPW2 (A17.5)
WBOL-OK (A17.7)
ALIS (A18.0)
ALRI (A18.1)
ALMX (A18.2)
AREM (A18.3)
ARGE (A18.4)
ARIS (A18.5)
The status signals related to the PLC inputs from sensors and switches are organized in the following five words of 16 bits, which can be addressed by ESO COMPUTER:
- CKELTU: word address 1F
Threshold signals from the analog sensors supply/conditioning electronic
units: each binary signal gives information if the measurement analog signal
ranges within the absolute minimum and maximum limits set in the electronic
unit (see figure 2).
1F/0 CKEL1RT 1F/1 CKEL2RT 1F/2 CKEL3RT 1F/3 CKEL4RT |
min/max thresholds of thermistors of rotating structure (RTMS) |
1F/4 CKEL1ST 1F/5 CKEL2ST 1F/6 CKEL3ST 1F/7 CKEL4ST |
min/max thresholds of thermistors of stationary structure (STMS) |
1F/8 CKEL1PT 1F/9 CKEL2PT 1F/10 CKEL3PT 1F/11 CKEL4PT |
min/max thresholds of thermistors of hydrostatic pads (PTMS) |
1F/12 CKEL1TT 1F/13 CKEL2TT |
min/max thresholds of thermistors of oil tank (TTMS) |
1F/14 CKELWT | min/max threshold of chilled water thermistor |
1F/15 - |
- OVF1: word address 20
Signals of overflow PLC analog input board.
20/0 OVF-RTT1 20/1 OVF-RTT2 20/2 OVF-RTT3 20/3 OVF-RTT4 |
overflow analog input RTT1 thermistor overflow analog input RTT2 thermistor overflow analog input RTT3 thermistor overflow analog input RTT4 thermistor |
20/4 OVF-STT1 20/5 OVF-STT2 20/6 OVF-STT3 20/7 OVF-STT4 |
overflow analog input STT1 thermistor overflow analog input STT2 thermistor overflow analog input STT3 thermistor overflow analog input STT4 thermistor |
20/8 OVF-PTT1 20/9 OVF-PTT2 20/10 OVF-PTT3 20/11 OVF-PTT4 |
overflow analog input PTT1 thermistor overflow analog input PTT2 thermistor overflow analog input PTT3 thermistor overflow analog input PTT4 thermistor |
20/12 OVF-TTT1 20/13 OVF-TTT2 |
overflow analog input input TTT1 thermistor overflow analog input input TTT2 thermistor |
20/14 OVF-WT | overflow analog input WT thermistor |
20/15 OVF-PROL | overflow analog input PROL thermistor |
- OVF2: word address 21
Signals of overflow PLC analog input boards.
21/0 OVF-PHVV | overflow analog input PHVV thermistor |
21/1 OVF-PHTU | overflow analog input PHTU thermistor |
21/2 OVF-RN1 | overflow analog input RN1 thermistor |
21/3 OVF-RN2 |
21/4 21/5 21/6 21/7 21/8 21/9 21/10 21/11 21/12 21/13 21/14 21/15 |
- - - - - - - - - - - - |
- FTRNOL: word address 22
22/0 22/1 22/2 22/3 22/4 22/5 22/6 22/7 22/8 22/9 22/10 22/11 22/12 22/13 22/14 22/15 |
SWRGH01 SWRGH02 FLHORN LZOLRC1 LZOLRC2 LMOLRC SWASFT1 SWASFT2 SWABFT1 SWABFT2 SWMDFT3 SWMDFT4 SWABFT3 SWABFT4 SWMPRC1 SWMPRC2 |
- PWOLID: word address 23
Signals of the ON-OFF sensors located in the oil feed unit and in the hydrostatic
support system and of the sensors in the electrical cabinets.
23/0 23/1 23/2 23/3 23/4 23/5 23/6 23/7 23/8 23/9 23/10 23/11 23/12 23/13 23/14 23/15 |
PSMNOL1 PSMNOL2 PSMSOLID PSMNOLID LZOLFT FLOLFT SWMPPW1 SWMPPW2 CKTMOLFT - AQVEQQ CKPWEL CKPWTL CKPWVV CKSIGECC - |
Anemometric switch of the cabinet fan Presence of +/- 24Vdc supply to electronic units Presence of 110Vac supply to power relay Presence of 24Vac supply to chilled water regulation valves |
The ALARM/WARNING codes, identified by integer numbers in decreasing priority order, are listed and explained below:
fault |
---|
no. | code | Name | Description |
---|---|---|---|
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 |
1 2 3 4 5 6 7 8 9 A B C D E F 10 11 12 13 14 15 16 17 18 19 1A 1B 1C 1D 1E |
ALPSMNID ALPSMSID ALPWTL ALPWEL ALPWVV ALPSMN1 ALPSMN2 - ALPSMSOL ALLZOLFT ALTMOLFT ALTUMIRT ALTUMIST ALTUMIPT ALTUMITT - ALSZMPPW ALMPPW1 ALMPPW2 ALTMHO ALDAAG ALDAMAX ALELTU ALFLOLFT ALMPRC1 ALMPRC2 ALSZMPRC ALLZOLRC ALLMOLRC ALRFVV |
Min pressure hydrostatic pads Max pressure hydrostatic pads 110 Vac supply breakdown 24 Vdc supply breakdown 24 Vac supply breakdown Min pressure oil feed pump 1 Min pressure oil feed pump 2 free Max pressure oil feed pumps 1 and 2 Min level conditioned oil tank Max temperature conditioned oil Thermistors out of tolerance (RTMS) Thermistors out of tolerance (STMS) Thermistors out of tolerance (PTMS) Thermistors out of tolerance (TTMS) Free Wrong selection of oil feed pumps1 and 2 Oil feed pump1 failure Oil feed pump2 failure Max temperature chilled water Wrong A/D conversion of the analog measurement signals Max range of analog measure min/max thershold alarm intervention min flow of filtered and conditioned oil Oil filtering pump 1 failure Oil filtering pump 2 failure Wrong selection of oil filtering pumps 1 and 2 Min level oil drain tank Max level oil drain tank Valve adjustment not completed |
fault |
---|
no. | code | Name | Description |
---|---|---|---|
31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 |
1F 20 21 22 23 24 25 26 27 28 29 2A 2B 2C 2D 2E 2F 30 31 32 |
ALASFT1 ALASFT2 ALMDFT3 ALMDFT4 ALFHORN ALSZRGHO ALTR ALSIGE ALSIEL ALWB - - SGASFT1 SGASFT2 SGMDFT3 SGMDFT4 ALSZFTAS ALSZFTMD ALAQVEQQ SGMITU |
Inlet filter clogged (alarm) Inlet filter 2 clogged (alarm) Delivery filter 3 clogged (alarm) Delivery filter 4 clogged (alarm) Min flow chilled water Wrong selection of chilled water regulation valves1 and 2 Faulty data transmission to ESO computer Faulty connectors to BSC cabinet Faulty connectors to ESO interface Oil adjustment not completed Free Free Filter 1 clogged (warning) Filter 2 clogged (warning) Filter 3 clogged (warning) Filter 4 clogged (warning) Wrong selection of the filters 1 and 2 Wrong selection of the filters 3 and 4 Absence of ventilation inside electrical cabinet Mean temp. computation not considering all involved temp. sensors |
In the word TUMI, address 24h, is stored the information about the thermistors
considered by the PLC for the computation of the mean values of temperatures:
for each thermistor one bit of the word TUMI is used to indicate whether
the thermistor analog signal is "in tolerance" or not:
Bit = 1 :
thermistor in tolerance for mean temperature computation
Bit = 2 :
thermistor out of tolerance for mean temperature computation
24/0
24/1
24/2
24/3TU1MIRT
TU2MIRT
TU3MIRT
TU4MIRTThermistors considered for the temperature mean value computation
of the zone RTMS
24/4
24/5
24/6
24/7TU1MIST
TU2MIST
TU3MIST
TU4MISTThermistors considered for the temperature mean value computation
of the zone STMS
24/8
24/9
24/10
24/11TU1MIPT
TU2MIPT
TU3MIPT
TU4MIPTThermistors considered for the temperature mean value computation
of the zone PTMS
24/12
24/13
24/14
24/15TU1MITT
TU2MITT
-
-Thermistors considered for the temperature mean value computation
of the zone TTMS
The following measurement signals and reference signal and mean values computed
by
PLC:
- - - - - - |
14 temperature signals of thermistors 3 average structure temperature signals rotating structure temperature (RTMS) stationary structure temperature (STMS) hydrostatic pads temperature (PTMS) 1 oil tank average temperature signal (TTMS) reference temperature for oil conditioning 1 position reference signal to the selected chilled water regulation valve hydrostatic pads oil pressure |
are defined and called with different binary (exadecimal) address:
ADDRESS | DEFINITION |
---|---|
1 2 3 4 5 6 7 8 9 A B C D E F 10 11 12 13 14 15 16 17 18 |
Rotating structure temperature transducer 1 Rotating structure temperature transducer 2 Rotating structure temperature transducer 3 Rotating structure temperature transducer 4 Stationary structure temperature transducer 1 structure temperature transducer 2 structure temperature transducer 3 structure temperature transducer 4 Pads temperature transducer 1 Pads temperature transducer 2 Pads temperature transducer 3 Pads temperature transducer 4 Oil tank temperature transducer 1 Oil tank temperature transducer 2 H2O temperature Average rotating structure temperature Average stationary structure temperature Average hydrostatic pads temperature Average oil tank temperature Reference temperature (for oil regulation) H2O regulation valve reference Hydrostatic pads oil pressure RN 1 RN 2 |
The measurement data are given in binary form: the temperature values are in 1/10 of degree centigrade, the pressure value in 1/10 of bar and the valve position reference in % of max reference.
The addresses are called by ESO COMPUTER.
the following INNSE adaptor cards are used:
The INNSE cards 9816.22786 and 9816.22787 require a 5V TTL externally supplied by ESO COMPUTER on pins AA (+5V) and BB(OV) of connector J4 of the INNSE rack.
INNSE suggests to put the small rack containing these adaptor cards (1+3 cards) inside the cabinets, that contains the ESO COMPUTER I/O interface rack, as shown in figure 3, to reduce the length of the transmission line at 5V and to carry outside the cabinet the 24V line, which is less sensitive to disturbances; this solution will be available with the final cabinet. For the tests in INNSE shop of Brescia, the interconnections will be tested with a simulator provided by INNSE.
The cards are contained in a panel-mountable rack having these max overall
dimensions
(see enclosed drawing - figure 6):
length = 395 mm
height = 132,5 mm
depth = 255 mm
The signal transmission protocols are two:
- direct transmission of the signals listed in the groups 1 and 2
- multiplexed-parallel transmission of the signals listed in the groups 3,
4 and 5.
For what concern the alarm/warning and status signals, there are approximately 50 signals stored in the PLC memory.
The faults occurring in the electrical and hydraulic equipments (BSC, POU, HSS, TMS) (both permanent and transient) are latched by the PLC and are associated to alarm binary codes stored in dedicated PLC memory areas.
The alarms are divided in three groups:
- the non-immediate alarms (called warnings)
- the immediate electronic alarms (called alarms type 1)
- the immediate mechanical and hydraulic alarms (called alarms type 2).
For the warnings and for the immediate alarms type 1 and 2 two direct logic signals are assigned, which are used by the PLC to inform the ESO computer that a fault occurred (direct signals ALRI and ALIS).
An additional direct logic signal is used (namely "multiple alarm/warning" ALMX) to indicate that more than one fault has been latched.
The ESO computer, receiving the alarm information from one or more of the two above direct signals, sends to the PLC an alarm code requirement using a dedicated ADDRESS code, 30d = 1Eh.
The PLC, after acquisition of the alarm/warning address 30d code, transmits
the alarm code through the DATA lines.
If multiple alarms occur, the direct signal "MULTIPLE ALARMS" is in logic
state1 and the ESO computer requires the transmission of the other alarms
by sending again the alarm ADDRESS code until the "MULTIPLE ALARMS" signal
is cleared by the PLC.
The multiple alarms/warnings codes transmission is made with a code related
priority logic.
The highest priority alarms are those coded with the lowest codes (1, 2, 3, etc.).
The reset of a latched alarm is made in two different ways:
- |
in local mode a RESET pushbutton located in the Local Control Panel clears the latched alarm only after the cause of the fault has been removed. |
- |
in remote mode under ESO computer control, a RESET logic signal is sent by the ESO computer to the PLC having the same function of the RESET pushbutton (direct signal RPAL). |
The status signals related to the inputs to the PLC from the hydraulic unit
(POU), from hydraulic support system (HSS), from temperature measuring system
(TMS) and from the electrical cabinet (BSC) are stored in a table, organized
in 16 bit words, inside the PLC memory.
The status words are listed in the group 3.
The ESO COMPUTER can address the transmission of each of these 16-bits status
words (which represent the image of the PLC inputs), using the 8 address lines
(starting from address 50).
The analog measurement signals from thermistors and reference signals for temperature and chilled water, listed in the group 5, are transmitted by the PLC in multiplexed-parallel form, addressed by the ESO COMPUTER.
The transmission protocol is described below:
The multiplexed-parallel transmission system consists of the following interface for alarm and status signals and measurement signals (see figure 4):
- |
8 ADDRESS lines: lines0-6 for address binary code definition, to address up to 128 codes and line7 for ADDRESS PARITY bit (ODD PARUTY). |
|
PLC inputs |
E12.0 - E12.6 E12.7 |
ADDRESS ADDRESS PARITY |
- |
18 DATA lines: lines0-15 for binary data definition and lines16 and 17 for two DATA PARITY bits (LOW for 0 to 7 DATA bits and high for 8 to 15 DATA bits, ODD PARITY). |
|
PLC outputs |
A12.0 - A13.7 A14.0 A14.1 |
DATA DATA PARITY LOW DATA PARITY HIGH |
- |
ADDRESS STROBE line PLC input E 13.0 |
- |
DATA STROBE line PLC output A 14.2 |
- |
ADDRESS ACKNOWLEDGE line PLC output A 14.3 |
- |
DATA ACKNOWLEDGE line PLC input E 13.1 |
- |
ADDRESS PARITY ERROR line PLC output A 14.4 |
ESO computer handles the ADDRESS lines, while the SIMATIC PLC handles the DATA lines.
Both the ADDRESS and DATA information are strobed with an ADDRESS STROBE and DATA STROBE signals, which are cancelled by sending an ADDRESS ACKNOWLEDGE and a DATA ACKNOWLEDGE signal respectively.
In case PLC detects a parity error in the ADDRESS transmission from ESO computer, it sends back the ADDRESS ACKNOWLEDGE signal plus the ADDRESS PARITY ERROR signal, which is held in logic state1 since the moment of parity error detection.
After ESO computer detects the ADDRESS PARITY ERROR signal, it sends the ADDRESS code255, which means to put all the 8 ADDRESS lines at logic state1.
The following scenarios are defined:
a) If 1 or more ADDRESS lines are detected by the PLC at logic level 0 (which means the address code detected is different from 255), the PLC transmits the ADDRESS ACKNOWLEDGE signal maintaining the ADDRESS PARITY ERROR signal at logic level1.
The PLC retransmits the detected ADDRESS code, different from 255, to ESO
computer through the DATA lines.
For sake of security the ADDRESS code will be sent both on the DATA byte LOW
(0-7) and on the DATA byte HIGH (8-15), transmitting also the DATA PARITY
bits.
Example:
if the PLC detects the ADDRESS code: BE = 1 0 1 1 1 1 1 0 (LSB)
it will send-back through the DATA lines the following code:
BE B E 11 = 10111110 - 10111110 - 1 - 1
data lines 0 7 8 15 16 17
This information will enable the ESO computer to detect the interrupted line(s).
The ADDRESS PARITY ERROR signal will be maintained at logic state1 until the correct ADDRESS transmission has been detected.
b) If no parity errors are detected (that means the PLC detects the ADDRESS
255), the PLC sends back the ADDRESS ACKNOWLEDGE signal and resets the ADDRESS
PARITY ERROR signal.
In this case the ESO computer retransmits the last ADDRESS code, which originated
the parity error alarm.
For the control of the DATA correct transmission from PLC, the ESO computer sends two dedicated ADDRESS codes to the PLC if any circumnstance is required (e.g. at every system start-up, after detection of a DATA PARITY ERROR, etc.).
These dedicated address codes, namely 119d = 77h, 120d = 78h, are recognized by the PLC as requests to send the following DATA:
119d = 0 0 0 0 - 0 - 0 (parity bits)
120d = F F F F - 1 - 1 (parity bits)
it will enable the ESO computer to check any error transmission or interruption in the DATA lines.
The proposed timing diagram of the ADDRESS and DATA information interchange is shown in figure4 (estimated length of the Strobe signals due to the PLC cycle time: approx. 50msec).
ESO computer forms and transmits ADDRESS code and ADDRESS STROBE signal
in the same instant.
PLC detects the ADDRESS STROBE high and after a delay (tipically 5msec.),
which eliminates the possible transients due to the optoinsulators and input
stage, latched the ADDRESS code and sends the ADDRESS ACKNOWLEDGE signal,
which is used by ESO computer to reset ADDRESS and STROBE lines.
On the other hand the PLC forms and transmits DATA and DATA STROBE signal
in the same instant.
ESO Computer detects the DATA STROBE signal at logic state1 and after the
same delay (tipically 5msec.) latches the DATA value and sends the DATA ACKNOWLEDGE
signal, which is used by PLC to reset the DATA and STROBE lines.
The following interlock contacts are provided by BSC to ESO COMPUTER cabinet:
- |
no.1 Potter-like relay contact, normally closed when the relay coil is powered, which is opened when are manually activated: |
Both relay contacts are open when the BSC main supply (380V, 50Hz 3-phase line) is open. |
|
|
|
- |
no.1 Potter-like relay contact, normally closed when the relay coil is powered, which is immediately opened when the power supply to the PLC CPU (220 Vac) and/or to the PLC interface (24 Vdc) fails. In this case no controlled shutdown procedure is possible to the BSC unit. |
INNSE suggests the following interlocks to be provided by ESO COMPUTER cabinet to BSC:
- |
no.1 relay contact (Potter-like relay), normally closed when the relay is powered, which immediately opens when a GENERAL STOP command is activated in the ESO cabinet. |
- |
1 relay contact (Potter-like relay), normally closed when the relay is powered, which immediately opens when an EMERGENCY STOP command is activated in the ESO cabinet. |
This contact is always active both in LOCAL and REMOTE mode of operation. |
The contacts must be suitable to operate with a nominal operating voltage of 24 Vdc and a current of 1 Amp. |
The two contacts (two wires for each contact) are available to the BSC cabinet: four pins are provided in the external interface to ESO COMPUTER connector J9 located in the BSC unit.
TITLE/ SUB-TITLE | SHT NUMBER | LAST UPDATE | DRAWING NUMBER |
HB Piping | HBPIP.DWG | ||
HB Valves and Sensors | HBVASENS.DWG | ||
HB Multiplexed Interface | HBMPXINT.DWG | ||
HB Parallel Interface | HBMPARINT.DWG | ||
HB Thermistors | HBTHM.DWG | ||
HB Interconnection 1 | HBINT1.DWG | ||
HB Timing | HBTIM.DWG | ||
HB Interconnection 2 | HBINT2.DWG |
![]() ![]() ![]() ![]() ![]() ![]() ![]() |